應(yīng)用領(lǐng)域
雙電源自動轉(zhuǎn)換開關(guān),顧名思義它是在用電突然斷電時通過雙電源切換開關(guān),自動連接到備用的電源上,使我們的運作不至于停斷,仍能繼續(xù)運作。雙電源自動轉(zhuǎn)換開關(guān)的用途,簡單來說就是一路常用一路備用,當常用電突然故障或停電時,通過雙電源
切換開關(guān),自動投入到備用電源上,(小負荷下備用電源也可由發(fā)電機供電)使設(shè)備仍能正常運行。常見的是電梯、消防、監(jiān)控上,銀行用的UPS不間斷電源也是,不過他的備用是電池組。
ATS適合應(yīng)用于建筑領(lǐng)域消防等關(guān)鍵負荷的雙電源供應(yīng),EPS適合應(yīng)用于EPS是以解決應(yīng)急照明、事故照明、消防設(shè)施等一級負荷供電設(shè)備為主要目標,提供一種符合消防規(guī)范的具有獨立回路的應(yīng)急供電系統(tǒng)。UPS主要是為IT行業(yè)設(shè)備提供用電,提供純凈、不間斷的后備電源。柴油發(fā)電機供電方式適合應(yīng)用于在需要長時間后備電源的供電場所與ATS、EPS、UPS配合使用。
雙電源作規(guī)程
1、當因故停電,且在較短時間內(nèi)無法恢復(fù)供電時,必須啟用備用電源。
步驟:
①切除市電供電各斷路器(包括配電室控制柜各斷路器,雙電源切換箱市供電斷電器),拉開雙投防倒送開關(guān)至自備電源一側(cè),保持雙電源切換箱內(nèi)自備電供電斷路器處于斷開狀態(tài)。
②啟動備用電源(柴油發(fā)電機組),待機組運轉(zhuǎn)正常時,順序閉合發(fā)電機空氣開關(guān)、自備電源控制柜內(nèi)各斷路器。
③逐個閉合電源切換箱內(nèi)各備用電源斷路器,向各負載送電。
④備用電源運行期間,操作值班人員不得離開發(fā)電機組,并根據(jù)負荷的變化及時調(diào)整電壓、廠頻率等,發(fā)現(xiàn)異常及時處理。
2、市電恢復(fù)供電時,應(yīng)及時做好電源轉(zhuǎn)換工作,切斷備用電源,恢復(fù)市電供電。
步驟:
①按順序逐個斷開自備電源各斷路器,順序是:雙電源切換箱自備電源斷路器→自備電源配電柜各斷路器→發(fā)電機總開關(guān)→將雙投開關(guān)撥至市電供電一側(cè)。
②按柴油機停機步驟停機。
③按順序,從市電供電總開關(guān)至各分路開關(guān)逐個閉合各斷路器,將雙電源切換箱自市電供電斷路器置于閉合位置