本產(chǎn)品可實現(xiàn)0.1-55KW任意值可調(diào)
| GLOK1-12C/3P/S0.4 02M |
| GLOK1-12C/3P/S1 02M |
| GLOK1-12C/3P/S2.5 02M |
| GLOK1-12C/3P/S4 02M |
| GLOK1-12C/3P/S6.3 02M |
| GLOK1-12C/3P/S12 02M |
| GLOK1-16C/3P/S16 02M |
| GLOK1-16CF/3P/S16 02M |
| GLOK1-16CL/3P/S16 02M |
| GLOK1-16CG/3P/S16 02M |
| GLOK1-32CG/3P/S32 02M |
| GLOK1-32CG/3P/S25 02M |
| GLOK1-32CG/3P/S18 02M |
| GLOK1-32CL/3P/S18 02M |
| GLOK1-32CF/3P/S18 02M |
| GLOK1-32CF/3P/S25 02M |
| GLOK1-32CF/3P/S32 02M |
| GLOK1-32CL/3P/S32 02M |
| GLOK1-45CL/3P/S45 02M |
| GLOK1-45CL/3P/S40 02M |
| GLOK1-45C/3P/S40 02M |
| GLOK1-45C/3P/S45 02M |
| GLOK1-45CF/3P/S45 02M |
| GLOK1-45CF/3P/S40 02M |
| GLOK1-45CG/3P/S40 02M |
| GLOK1-45CG/3P/S45 02M |
| GLOK1-63CG/3P/S50 02M |
| GLOK1-63CG/3P/S63 02M |
| GLOK1-63CL/3P/S63 02M |
| GLOK1-63CL/3P/S50 02M |
| GLOK1-63CF/3P/S50 02M |
| GLOK1-63CF/3P/S63 02M |
| GLOK1-100CF/3P/S80 02M |
| GLOK1-100CF/3P/S100 02M |
| GLOK1-100CL/3P/S100 02M |
| GLOK1-100CL/3P/S80 02M |
| GLOK1-100CG/3P/S80 02M |
| GLOK1-100CG/3P/S100 02M |
| GLOK1-125CG/3P/S125 02M |
| GLOK1-125CL/3P/S125 02M |
| GLOK1-125CF/3P/S125 02M |
| GLOK1-125C/3P/S125 02M |
產(chǎn)品功能
◇特大短路瞬時保護:保護電流與開關主體額定電流有關,其整定電流為20In±20%、動作時間t4≤2~3ms。
◇短路瞬時保護:保護電流與電子脫扣器額定工作電流有關,其整定電流為16In±15%、動作時間t3≤0.1ms。
◇短路短延時或定時限保護:保護電流與電子脫扣器額定工作電流有關,其整定電流面板上可調(diào)(6~12Ir1)±15%(電動機保護)、(3~6Ir1)±10%(配電保護)、延時動作整定時間t2=0.2s
◇過載長延時保護:保護電流與電子脫扣器額定工作電流有關,其整定電流Ir1面板可調(diào)0.4~1Ie,反時限特性為I2T=(1.5Ir1)2t1, t1為長延時電流1.5Ir1時的整定時間,配電用t1=64s,電動機用t1=128s
◇缺相、斷相保護:動作整定時間為2s
◇三相不平衡保護:任意二相電流相差50%,動作整定時間為2s
◇過壓保護:三相470±10V,動作整定時間5s
◇欠壓保護:三相270±10V,動作整定時間5s
◇啟動延時:短路短延時或定時限不保護,整定時間為2s
◇消防接口:直流24V消防接口輸出(可選)
◇漏電保護:剩余電流根據(jù)客戶要求定制,動作時間≤0.1s(延時型為0.3s)(可選)
◇預報警功能:電流可調(diào)
◇在線編程功能
◇故障指示 ◇試驗功能